Work area telecommunications outlet / connector
Each four - pair horizontal cable shall be terminated in an eight-position modular jack at the work area. The telecommunications outlet/connector shall meet the modular interface requirements specified in IEC 60603-7-1, IEC 60603-7-2, IEC 60603-7-3, IEC 60603-7-4 and IEC 60603-7-5. In addition, the telecommunications outlet/connector shall meet the requirements of clause 5.7 and the terminal marking and moounting requirements specified in ANS/TIA-570-B. Pin.pair assignments shall be as shown in Figure 1 or, optionally, per Figure 2 if necessary to accommodate certain cabling systems. The colors shown are associated with the horizontal distribution cable shown in Table 2. These figures depict the front view of the telecommunications outlet/connector.
Each four - pair horizontal cable shall be terminated in an eight-position modular jack at the work area. The telecommunications outlet/connector shall meet the modular interface requirements specified in IEC 60603-7-1, IEC 60603-7-2, IEC 60603-7-3, IEC 60603-7-4 and IEC 60603-7-5. In addition, the telecommunications outlet/connector shall meet the requirements of clause 5.7 and the terminal marking and moounting requirements specified in ANS/TIA-570-B. Pin.pair assignments shall be as shown in Figure 1 or, optionally, per Figure 2 if necessary to accommodate certain cabling systems. The colors shown are associated with the horizontal distribution cable shown in Table 2. These figures depict the front view of the telecommunications outlet/connector.